Monitor environmental sensors
Temperature, humidity and instantaneous power are measurements, usually stored as
GAUGE. Cumulative energy or event totals may require a counter type instead.
Check each object’s units, identity and semantics before choosing a template.
Check what already ships before you write anything.
What ships
Section titled “What ships”Only four data query definitions live in the tree’s own query directory, and none of them is environmental.
| Shipped SNMP query | Covers |
|---|---|
interface.xml |
Network interfaces |
host_disk.xml |
Host Resources storage |
net-snmp_disk.xml |
UCD declared partitions |
net-snmp_devio.xml |
UCD block device I/O |
Sensor coverage arrives two other ways.
Script-server queries, bundled in the Net-SNMP device package. Import
install/templates/NetSNMP_Device.xml.gz to deploy its three lmSensors query XML
files under resource/script_server/. The helper
scripts/ss_netsnmp_lmsensors.php also exists in the source checkout.
| Query | Table |
|---|---|
| Net-SNMP - Sensors - Get Thermal Sensors | .1.3.6.1.4.1.2021.13.16.2.1 |
| Net-SNMP - Sensors - Get Fan Sensors | .1.3.6.1.4.1.2021.13.16.3.1 |
| Net-SNMP - Sensors - Get Voltage Sensors | .1.3.6.1.4.1.2021.13.16.4.1 |
The helper uses index, name and reading columns. The query indexes on numeric
sensorDevice; sensorName supplies a display name that the helper truncates to
18 characters. Names are not guaranteed unique sensor identities.
The normal get sensorReading path returns raw values: millidegrees for the legacy
temperature object, millivolts for voltage, and RPM for fans. The thermal graph
applies a Divide by 1000 CDEF. The voltage graph has no CDEF despite its Volts
label, a confirmed scaling bug.
The separate query sensorReading path scales temperature and voltage, and attempts
signed voltage conversion using the incorrect constant 4294967294. It can also
throw on unavailable readings.
Do not infer stored units from this discovery output.
The helper still uses legacy temperature column .2.1.3. Current upstream
LM-SENSORS-MIB
deprecates that unsigned object in favor of signed column .2.1.4; verify support
and negative-temperature behavior on the actual agent before adapting a template.
Device packages, shipped as importable archives. Several carry their own query XML and write it into the query directories at import time. The ones that matter here:
| Package | Brings |
|---|---|
| SNMP UPS | UPS-MIB input and output line queries, plus fixed-OID templates for battery, runtime, temperature and alarms |
| AKCP Device | Script queries for temperature, humidity, airflow and 4-20 mA sensors |
| APC InfraStruXure PDU | Queries for breaker and phase statistics |
| APC InfraStruXure InRow CRAC | Queries for unit and group statistics, including temperatures, humidity, airflow and fan speed |
| BayTech PDU | An outlet query and a three-phase circuit query, with current, voltage, power and temperature |
Inspect the matching package before writing a query by hand. Follow Import and export templates, verify file deployment and discovery, then explicitly create the desired graphs. Package presence does not prove device compatibility or correct scaling; the UPS and lmSensors defects below need attention.
The two shapes a sensor takes
Section titled “The two shapes a sensor takes”For SNMP collection, distinguish scalar objects from indexed table instances.
A fixed OID. One scalar value at one address, the same address on every device of that type. Battery temperature. Total output power. Use a fixed-OID data source: an SNMP get against a literal OID, and one data source per reading.
A table. An unknown number of readings discovered per device. Rack probes, outlet strips, per-phase measurements. Use a data query, which walks the table, learns the index, and lets you pick which rows become graphs.
The shipped UPS package uses both. Follow the MIB’s object structure: a device with only one current probe may still expose it as an indexed table row.
| UPS reading | Shape | OID |
|---|---|---|
| Battery temperature | Fixed | .1.3.6.1.2.1.33.1.2.7.0 |
| Estimated runtime remaining | Fixed | .1.3.6.1.2.1.33.1.2.3.0 |
| Time on battery | Fixed | .1.3.6.1.2.1.33.1.2.2.0 |
| Battery voltage | Fixed | .1.3.6.1.2.1.33.1.2.5.0 |
| Alarms present | Fixed | .1.3.6.1.2.1.33.1.6.1.0 |
| Input voltage, current, power, frequency | Query | .1.3.6.1.2.1.33.1.3.3.1 |
| Output voltage, current, power, load | Query | .1.3.6.1.2.1.33.1.4.4.1 |
Every one of those data sources is a GAUGE. None is a counter. The shipped
template archive declares a 60-second step and 600-second heartbeat, a minimum of
zero, and no maximum, except temperature, which has no minimum. Check the imported
profile and actual RRD configuration; these declarations do not establish the
running poll cadence. A valid negative reading also needs a graph axis that shows it.
Find the OIDs
Section titled “Find the OIDs”Walk the device before you write anything. You are looking for three things: a table of readings, a parallel table of labels, and whatever multiplier the vendor chose, plus validity/status objects where available.
snmpwalk -v2c -c public probe.example.net .1.3.6.1.2.1.33# Replace this example enterprise number with the vendor's actual number.vendor_oid='.1.3.6.1.4.1.318'snmpwalk -v2c -c public probe.example.net "$vendor_oid"Replace the example host and community with configured values and run probes from the poller. Load the matching MIB and dependencies to inspect names, units and semantics; vendor object documentation can also explain numeric OIDs. A nearby threshold or status code is not interchangeable with a measurement.
snmptranslate -m +UPS-MIB -Td -OS .1.3.6.1.2.1.33.1.2.7The MIB definition is where the scaling is documented. A vendor that reports tenths of a degree will say so in the object’s description or units clause, and in associated vendor documentation. Guessing from one reading can turn 23.5 degrees into a graph of 235.
Standard MIBs cover more than people expect. UPS-MIB at .1.3.6.1.2.1.33 is
generic across vendors. ENTITY-SENSOR-MIB gives a sensor value with its own
scale and precision fields alongside it. Check for those before reaching for an
enterprise subtree.
Compare discovery across representative reboots and probe changes in a test installation. Two unchanged walks alone do not prove index stability. Record stable sensor identities where available before creating long-lived graphs.
Build a fixed-OID data source
Section titled “Build a fixed-OID data source”A fixed-OID sensor needs a data template using the SNMP get data input, with the
OID as a literal value and one data source item in it. Set the type to GAUGE,
give the minimum a real value only when the sensor genuinely cannot go below it,
and leave the maximum undefined unless the vendor documents a ceiling.
Values outside RRD data-source bounds become unknown. Set those bounds in the stored raw units, not the graph’s converted units; otherwise valid readings can be lost before a display CDEF is applied.
Build a data query
Section titled “Build a data query”A query needs an index OID, a way to turn each walked OID into an index, and one field per column you want.
The UPS output query is a short worked example. It indexes on the line table, parses the index off the end of each returned OID with a regular expression, and declares one input field for the index and four output fields for voltage, current, power and load. Output definitions include method, source, direction and column OID. A column OID can be a valid index-walk root; matching the query’s parser and the actual returned OIDs is what matters. See Data queries and indexes for how the index is chosen and stored.
Pick a reindex method deliberately. The choices are none, on uptime going backwards, on the index count changing, and Verify All Fields. Sensor tables are the case where the weaker methods fail: unplug one probe from a rack unit and plug in another, and the count may not change while every reading behind the index now belongs to a different sensor. Full verification costs SNMP work on each cycle. Verify which identity fields the query can check: unchanged numeric indexes or duplicate/truncated labels cannot prove that a physical probe is the same one. Refresh discovery and review graph associations after replacement.
Scale the value
Section titled “Scale the value”Decide where the conversion happens, and only put it in one place.
| Where | When to use it |
|---|---|
| In the collection script | Use a documented collector contract; lmSensors get currently returns raw units |
| In a CDEF on the graph item | The raw value is worth storing, and the display unit is a presentation choice |
A CDEF is the usual answer for a vendor multiplier. The shipped packages carry
definitions such as Divide By 10, built from the current data source, 10, and
division. Apply them only to objects with the corresponding raw unit.
The UPS package has incorrect power and time CDEFs: its On Battery series divides seconds by 6000 instead of 60, and input/output Watts series divide watts by 10. For a conforming agent, 600 seconds should display as 10 minutes and 1000 watts as 1000 watts. Battery voltage and line current do require division by 10; estimated runtime is already minutes. See RFC 1628’s UPS object units.
Storing the raw reading and dividing on the graph keeps the RRD file honest and lets you correct a display multiplier without rewriting raw history, provided the samples survived data-source bounds and retention. Collector-side conversion changes the stored unit and may discard precision; document it. Unexplained raw readings should not be presented as a verified engineering unit.
Do not apply the conversion twice. A CDEF on a graph whose script already scaled the value can produce a plausible but incorrect reading.
Give it graph settings that suit a measurement
Section titled “Give it graph settings that suit a measurement”Choose settings for the measurement instead of copying traffic defaults blindly.
| Setting | Traffic | Sensor |
|---|---|---|
| Data source type | COUNTER |
GAUGE |
| Base value | 1000, so the axis reads in k and M | Still 1000, but the prefix is meaningless on degrees |
| Autoscale | Wanted, since the range is unknown | Usually unwanted, since the range is known |
| Upper and lower limit | Depend on autoscale mode | Choose a useful visible range |
Set an explicit upper and lower limit and a vertical label that names the real
unit. The shipped UPS temperature graph does this: a lower limit of 0, an upper
limit of 100, and C as the vertical label.
The autoscale option is a set of choices, not a switch. The one the shipped
temperature graph uses passes a lower limit with --alt-autoscale-max; it does
not pass the stored upper limit of 100. Without rigid boundaries, an out-of-range
reading can expand a passed limit. A configured limit is not automatically pinned. Pick the variant
that keeps the boundary you care about:
| Option | Effect |
|---|---|
| Autoscale ignoring limits | Both ends float. Use when you have no idea of the range |
| Autoscale accepting a lower limit | Passes the lower limit; maximum follows data |
| Autoscale accepting an upper limit | Passes the upper limit; minimum follows data |
| Autoscale with both limits | Passes both limits; expansion still depends on rigid mode |
There is also a rigid boundaries option that stops the axis expanding when a value falls outside the limits you set. Turn it on when a fixed axis matters more than seeing the excursion, and leave it off when it does not, because a rigid graph can clip an excursion outside the displayed range. This does not delete the stored sample. See the RRDtool graph limits reference.
For degrees or percent where SI prefixes would confuse readers, consider a units exponent of 0. Base 1000 controls prefix steps; it does not itself disable prefixes or convert measurement units.
Consolidation matters more here than on traffic
Section titled “Consolidation matters more here than on traffic”An interface counter averaged over an hour still tells you roughly what happened.
A temperature averaged over an hour hides the ten minute excursion that mattered.
Make sure the storage profile behind these data sources keeps a MAX archive,
and configure the plotted series to read the appropriate MAX consolidation.
A legend maximum over an AVERAGE series does not recover the original peak.
Even a MAX archive only preserves peaks represented in collected samples; it cannot recover an excursion between polls or values rejected before storage. See Manage data retention and Data sources and archives.
When there is no MIB worth using
Section titled “When there is no MIB worth using”Plenty of environmental gear speaks Modbus, a serial protocol, or an HTTP API, and its SNMP agent exposes nothing useful. Those need a script data input. The script runs on the poller host, not on the device, and reaching the device is the script’s problem. See Write a data collection script for the output contract.
Return U rather than 0 when a sensor is unreachable. A probe that went offline
is not a probe reading zero degrees.
Failure modes
Section titled “Failure modes”| Symptom | Usual cause |
|---|---|
| Temperature graphed as a number ten or a hundred times too large | Vendor multiplier not divided out |
| Temperature graphed ten times too small | Divided twice, once in the script and once in a CDEF |
| A voltage rail reads as billions | An unsigned SNMP integer holding a negative value, uncorrected |
| Sensor graphs go flat after a probe is swapped | The table reindexed and the data source now points at a different sensor |
| Readings above a threshold appear as gaps | A maximum was set on the data source and real values exceed it |
| Axis labelled in k or M on a degree reading | Base value and unit settings inherited from a traffic template |
| An excursion is invisible on a week view | Check the selected consolidation, retained resolution, poll interval and rejected samples |
| A query returns no indexes | Check returned OIDs, parser matches, access restrictions and object support; a column root can be valid |
| The lmSensors queries find nothing on a Linux host | Check agent support, access, exposed sensor rows and exact SNMP errors |
Documentation license: CC BY-SA 4.0Site code license: GPL-3.0-or-laterKadupul is not affiliated with or endorsed by The Cacti Group.